Parameter Values (Range) Unit Step Default Description
5=off
Power unit Mult
3=k
6=M
3=k Unit multiplier for
presentation of the
power related val-
ues
Energy unit Mult
3=k
6=M
3=k Unit multiplier for
presentation of the
energy related val-
ues
Active power Dir
1=Forward
2=Reverse
1=Forward Direction of active
power flow: For-
ward, Reverse
Reactive power Dir
1=Forward
2=Reverse
1=Forward Direction of reac-
tive power flow:
Forward, Reverse
Power deadband 1000...10000 1 10000 Deadband configu-
ration value for in-
tegral calculation.
(percentage of Sn
as 0,001 % s)
Pulse quantity 1...10000000 Wh/VArh 1 100000 Pulse quantity for
the energy pulse
outputs
Table 1434: PEMMXU Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Forward Wh Initial 0...999999999 1 0 Preset Initial value
for forward active
energy
Reverse Wh Initial 0...999999999 1 0 Preset Initial value
for reverse active
energy
Forward VArh Initial 0...999999999 1 0 Preset Initial value
for forward reactive
energy
Reverse VArh Initial 0...999999999 1 0 Preset Initial value
for reverse reactive
energy
Measurement
mode
1=PhsA, PhsB, PhsC
2=Arone
3=Pos Seq
4=PhsAB
5=PhsBC
6=PhsCA
7=PhsA
8=PhsB
9=PhsC
1=PhsA, PhsB, PhsC Selected measure-
ment mode for
power calculation
Pulse on time 0.050...60.000 s 0.001 1.000 Energy accumula-
ted pulse ON time
in secs
Pulse off time 0.050...60.000 s 0.001 0.500 Energy accumula-
ted pulse OFF time
in secs