Table 1227: DNZSRDIR Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 1 20 Reset delay time
Min operate current 1.0...100.0 %In 0.1 10.0 Minimum operating
current
Min operate volt-
age
1.0...100.0 %Un 0.1 30.0 Minimum operating
voltage
Pol reversal
0=False
1=True
0=False Rotate polarizing
quantity
5.15.9 DNZSRDIR Monitored data
Table 1228: DNZSRDIR Monitored data
Name Type Values (Range) Unit Description
ANGLE_RCA FLOAT32 -180.00...180.00 deg Angle between operat-
ing angle and charac-
teristic angle
DNZSRDIR Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
5.16 Load blinder LBRDOB (ANSI 21LB)
5.16.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE
identification
Load blinder LBRDOB LB 21LB
5.16.2 Function block
Figure 734: Function block
Protection related functions
1MRS759142 F
1294 REX640
Technical Manual