ABB RELION REX640 - 10.2.5.1 Distortion measurement; 10.2.5.2 Total harmonic distortion

ABB RELION REX640
1960 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
U_A
U_B
U_C
U3P
Distortion
measure-
ment
Total
harmonic
distortion
Harmonic
calculation
SMNTHD_A
SMNTHD_B
SMNTHD_C
SMNDC_A
SMNDC_B
SMNDC_C
SMNH01_A
SMNH01_B
SMNH01_C
SMNH02_A
SMNH02_B
SMNH02_C
...unl hmax
Figure 964: Functional module diagram
10.2.5.1 Distortion measurement
The Distortion measurement module measures harmonics up to the 11
th
harmonic.
The filter used for harmonics includes a spectrum of frequencies near each
harmonic frequency. FFT for one period is used. The resulting frequency spectrum is
wider than in a harmonic subgroup. An anti-aliasing filter is used.
10.2.5.2 Total harmonic distortion
The total harmonic distortion THD is calculated from the measured harmonic
components with the formula
THD
I
I
h
h
n
=
=
1
2
2
(Equation 392)
I
h
h
th
harmonic component
I
1
Fundamental voltage (1
st
harmonic)
n Number of harmonics
THD shorter mean value outputs are SMNTHD_A, SMNTHD_B and SMNTHD_C. These
and also the 10-minute mean values LMNTHD_A, LMNTHD_B and LMNTHD_C are
seen in the monitored data. These values are always shown as percentage of
the fundamental frequency's phase-to-earth voltage 3-second mean value. The 10-
minute mean values also follow 10 min ticks. See also
Figure 965
and the description
for sliding values.
Power quality measurement functions
1MRS759142 F
1822 REX640
Technical Manual