3.24 Load profile LDPRLRC (ANSI LOADPROF)
3.24.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Load profile recorder LDPRLRC LOADPROF LOADPROF
3.24.2 Function block
Figure 188: Function block
3.24.3 Functionality
The protection relay is provided with a load profile recorder. The load profile feature
stores the historical load data captured at a periodical time interval (demand
interval). Up to 12 load quantities can be selected for recording and storing in a
nonvolatile memory. The value range for the recorded load quantities is about eight
times the nominal value, and values higher than that saturate. The recording time
depends on a settable demand interval parameter and the amount of quantities
selected. The record output is in the COMTRADE format.
3.24.3.1 Quantities
Table 341: Signals supported by the load profile recorder
Function Signal Description
CMMXU I_DMD_A Demand value of IL1 current
I_DMD_B Demand value of IL2 current
I_DMD_C Demand value of IL3 current
Table continues on the next page
1MRS759142 F Basic functions