X
R
Non -directional
α
α
(2
X1 zone x + X0 zone x)/3
(2
R1 zone x + R0 zone x)/3
-X1 reverse zone x
X1 zone x
* (2
X1 zone x + X0 zone x)/3
-X1 reverse zone x
X1 zone x
* (2
R1 zone x + R0 zone x)/3
Figure 544: Settings which define the line reach for phase-to-earth impedance
measuring elements if Impedance mode Zn = "Rectangular", non-directional
directionality
Impedance mode Zn = Polar
In case of phase-to-phase or three-phase impedance measuring elements, the line
reach is defined with:
Z1 zone x
(x = 1...5)
Z1 angle zone x
(x = 1...5)
In case of non-directional characteristics, the reactive reach magnitude in reverse
direction is defined with the
Z1 reverse zone x
(x = 1...5) setting. The characteristic
line angle,
Z1 angle zone x,
is the same for forward and reverse direction.
X
R
Forward
X
R
Reverse
X
R
Non-directional
Z1 angle zone x
Z1 angle zone x
Z1 angle zone x
Z1 angle zone x
Z1 reverse zone x
Z1 zone x
Z1 zone x
Z1 zone x
Figure 545: Settings which define the line reach for phase-to-phase or three-phase
impedance measuring elements if Impedance mode Zn = "Polar"
In case of phase-to-earth impedance measuring elements, the line reach is defined
with:
Z1 zone x
(x = 1...5)
1MRS759142 F
Protection functions
REX640
Technical Manual
971