Table 13: Non group settings
Parameter Values (Range) Unit Step Default Description
FB naming conven-
tion
1=IEC61850
2=IEC60617
3=ANSI
1=IEC61850 FB naming conven-
tion used in IED
Backlight timeout
1
1...60 min 1 3 LHMI backlight
timeout
Web HMI mode
0=Off
1=On
0=Off Web HMI function-
ality
HMI timeout 1...60 min 1 3 HMI login timeout
SLD symbol format
1=IEC
2=ANSI
1=IEC Single Line Dia-
gram symbol for-
mat
Setting visibility
1=Basic
2=Advanced
2=Advanced Setting visibility for
HMI
User defined name
0=Disabled
1=Enabled
false Configuration of
User defined name
3.1.8 HMI control settings
Confirmation dialog
If the parameter
Breaker operation
in Configuration> Control> HMI is set to "After
confirmation", a confirmation dialog box opens after tapping the control button.
The confirmation dialog box has a progress bar indicating the
Select timeout
set for
the controllable object. If the
Control mode
setting of a control function is set to
"sbo-with-enhanced-security", the confirmation dialog box always opens regardless
of the
Breaker operation
setting value.
Delayed close
If the parameter
Close delay
mode in Configuration> Control> LHMI is set to "In
use", a timer is started after tapping the close button and accepting the possible
confirmation dialog. Close operation is performed only after the timer reaches zero.
Remaining time is displayed on top of close button, user can cancel the operation
during countdown by tapping the Cancel button. The delay can be configured by
Close delay
in Configuration> Control> LHMI.
Table 14: HMI control settings
Parameter Values Unit Step Default Description
Close delay
mode
1=In use
2=Not in use
2=Not in use Delayed operation
when closing circuit
breakers, disconnec-
Table continues on the next page
1
SHMI has separate backlight timeout setting that is used while in switchgear view. The SHMI
setting can be accessed from SHMI settings page, that is available while in SHMI's switchgear
page.