Table 36: Protocol control in the protection relay
Parameter Options Description
Configuration/Communication/Proto-
cols/Network1/FTP
Off Denies FTP and FTPS
On Allows FTP and FTPS
Secure (Default) Allows FTPS only
Configuration/Communication/Proto-
cols/Network2/FTP
Off Denies FTP and FTPS
On Allows FTP and FTPS
Secure (Default) Allows FTPS only
Configuration/Communication/Proto-
cols/HMI Port/FTP
Off Denies FTP and FTPS
On Allows FTP and FTPS
Secure (Default) Allows FTPS only
Configuration/Communication/Proto-
cols/Network1/HTTPS
Off Denies HTTPS
On (Default) Allows HTTPS
Configuration/Communication/Proto-
cols/Network2/HTTPS
Off Denies HTTPS
On (Default) Allows HTTPS
Configuration/Communication/Proto-
cols/Network1/MMS
Off Denies IEC 61850 MMS
On (Default) Allows IEC 61850 MMS
Configuration/Communication/Proto-
cols/Network2/MMS
Off Denies IEC 61850 MMS
On (Default) Allows IEC 61850 MMS
Configuration/Communication/Proto-
cols/HMI Port/MMS
Off Denies IEC 61850 MMS
On (Default) Allows IEC 61850 MMS
Configuration/Communication/Proto-
cols/Network1/DNP
Off Denies DNP3
On (Default) Allows DNP3
Configuration/Communication/Proto-
cols/Network2/DNP
Off Denies DNP3
On (Default) Allows DNP3
Configuration/Communication/Proto-
cols/Network1/Modbus
Off Denies Modbus
On (Default) Allows Modbus
Configuration/Communication/Proto-
cols/Network2/Modbus
Off Denies Modbus
On (Default) Allows Modbus
Configuration/Communication/Proto-
cols/Network1/ IEC-60870-5-104
Off Denies IEC 60870-5-104
On (Default) Allows IEC 60870-5-104
Configuration/Communication/Proto-
cols/Network2/ IEC-60870-5-104
Off Denies IEC 60870-5-104
On (Default) Allows IEC 60870-5-104
3.2.6.3 Protocol write access rights
Write access rights are configurable for FTP, MMS, and HTTPS protocols in
Configuration> Authorization. The write access parameters are used to narrow
down services that allow setting changes on different network interfaces. Disabling
the FTP and IEC 61850 MMS write access on Network 1 and 2 prevents the user
from updating the configuration to the protection relay from PCM600. Disabling the
HTTPS write access prevents the user from writing setting changes from WHMI.