3.18.6 Received GOOSE interlocking information
GOOSERCV_INTL
3.18.6.1 Function block
Figure 99: Function block
3.18.6.2 Functionality
The received GOOSE interlocking information function GOOSERCV_INTL is used to
connect the GOOSE double binary input to the application and extracting single
binary position signals from the double binary position signal.
The OP output signal indicates that the position is open. Default value (0) is used if
VALID output indicates invalid status.
The CL output signal indicates that the position is closed. Default value (0) is used if
VALID output indicates invalid status.
The OK output signal indicates that the position is neither in faulty or intermediate
state. The default value (0) is used if VALID output indicates invalid status.
3.18.6.3 Signals
Table 149: GOOSERCV_INTL Input signals
Name Type Default Description
IN Dbpos 0 Input signal
Table 150: GOOSERCV_INTL Output signals
Name Type Description
OP BOOLEAN Position open output signal
CL BOOLEAN Position closed output signal
OK BOOLEAN Position OK output signal
VALID BOOLEAN Output signal
1MRS759142 F Basic functions
REX640
Technical Manual