ABB RELION REX640 - 9.10.5.9 Pulse control

ABB RELION REX640
1960 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
B
U
U
d
BW
=
( / )2
(Equation 384)
U
d
|U
m
– U
p
|, differential voltage
U
BW
Setting parameter
Band width voltage
t
T
B
=
( )
2
1
(Equation 385)
T T1 or T2
The monitored data UD_CTL shows the differential voltage value U
m
– U
p
. If the
value exceeds half of the
Band width voltage
setting and has a negative sign, a
raising pulse is issued. The UD_CTL monitored data can also be seen in the DT timer
mode.
The hysteresis approach is presented in
Figure 916
.
Figure 920: Inverse time characteristic for different values on T1 or T2 (The smaller
figure is a zoom-in of the larger one)
9.10.5.9 Pulse control
The tap changer generates an active operating signal when the tap-changing
process is active. This signal is used for alarming purposes and must be connected
1MRS759142 F
Control functions
REX640
Technical Manual
1715