6.6.6 Signals
6.6.6.1 MDSOPT Input signals
Table 1282: MDSOPT Input signals
Name Type Default Description
BLOCK BOOLEAN 0=False Block input status
POS_ACTIVE BOOLEAN 0=False When active indicates
the equipment is run-
ning
RESET BOOLEAN 0=False Resets the accumula-
ted operation time to
initial value
6.6.6.2 MDSOPT Output signals
Table 1283: MDSOPT Output signals
Name Type Description
ALARM BOOLEAN Alarm accumulated operation
time exceeds Alarm value
WARNING BOOLEAN Warning accumulated opera-
tion time exceeds Warning
value
6.6.7 MDSOPT Settings
Table 1284: MDSOPT Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Warning value 0...299999 h 1 8000 Warning value for
operation time su-
pervision
Alarm value 0...299999 h 1 10000 Alarm value for op-
eration time super-
vision
Table 1285: MDSOPT Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Initial value 0...299999 h 1 0 Initial value for op-
eration time super-
vision
Operating time
hour
0...23 h 1 0 Time of day when
alarm and warning
will occur
Operating time
mode
1=Immediate
2=Timed Warn
1=Immediate Operating time
mode for warning
and alarm
1MRS759142 F Supervision functions
REX640
Technical Manual
1341