ABB RELION REX640 - 4.3.5 High-impedance based restricted earth-fault protection HREFPDIF (ANSI 87 NHI); 4.3.5.1 Identification; 4.3.5.2 Function block; 4.3.5.3 Functionality

ABB RELION REX640
1960 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.3.4.10 Technical data
Table 687: LREFPNDF Technical data
Characteristic Value
Operation accuracy Depending on the frequency of the measured
current: f
n
±2 Hz
±2.5% of the set value or ±0.002 x I
n
Start time
1, 2
Minimum Typical Maximum
I
Fault
= 2.0 × set
Oper-
ate value
37 ms 41 ms 45 ms
Reset time Typically 40 ms
Reset ratio Typically 0.96
Retardation time <35 ms
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Suppression of harmonics DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5, …
4.3.5 High-impedance based restricted earth-fault protection
HREFPDIF (ANSI 87NHI)
4.3.5.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
High-impedance based restricted
earth-fault protection
HREFPDIF dIoHi> 87NHI
4.3.5.2 Function block
Figure 431: Function block
4.3.5.3 Functionality
The high-impedance based restricted earth-fault protection function HREFPDIF
is used for the restricted earth-fault protection of generators and power
transformers.
The function starts when the differential neutral current exceeds the set limit.
HREFPDIF operates with the DT characteristic.
1
Current before fault = 0.0, f
n
= 50 Hz, results based on statistical distribution of 1000 measure-
ments
2
Includes the delay of the signal output contact
1MRS759142 F Protection functions
REX640
Technical Manual
759