Settings
Table 203: TPMGAPC Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Pulse time 0...2880 min 1 0 Minimum
pulse time
Technical revision history
Table 204: TPMGAPC Technical revision history
Product connectivity
level
Technical revision Change
PCL2 E Changed the maximum pulse time from 5 h
to 48 h
3.20.2 Pulse timer, eight channels PTGAPC (ANSI 62PT)
3.20.2.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Pulse timer, eight channels PTGAPC PT 62PT
3.20.2.2 Function block
Figure 126: Function block
3.20.2.3 Functionality
The pulse timer function PTGAPC contains eight independent timers. The function
has a settable pulse length. Once the input is activated, the output is set for a
specific duration using the
Pulse delay time
setting.
1MRS759142 F
Basic functions
REX640
Technical Manual
235