DPHHPDOC Input signals
Table 399: DPHHPDOC Input signals
Name Type Default Description
I3P SIGNAL - Three-phase currents
U3P SIGNAL - Three-phase voltages
BLOCK BOOLEAN 0=False Block signal for acti-
vating the blocking
mode
ENA_MULT BOOLEAN 0=False Enable signal for cur-
rent multiplier
NON_DIR BOOLEAN 0=False Forces protection to
non-directional
DPHLPDOC Output signals
Table 400: DPHLPDOC Output signals
Name Type Description
OPERATE BOOLEAN Operate
START BOOLEAN Start
FAULT_DIR Enum Detected fault direction
DIRECTION Enum Direction information
DPHHPDOC Output signals
Table 401: DPHHPDOC Output signals
Name Type Description
OPERATE BOOLEAN Operate
START BOOLEAN Start
FAULT_DIR Enum Detected fault direction
DIRECTION Enum Direction information
4.1.2.10 Settings
DPHLPDOC Settings
Table 402: DPHLPDOC Group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Start value 0.05...10.00 xIn 0.01 0.05 Start value
Start value Mult 0.8...10.0 0.1 1.0 Multiplier for scal-
ing the start value
Time multiplier 0.025...15.000 0.005 1.000 Time multiplier
in IEC/ANSI IDMT
curves
Table continues on the next page
Protection functions 1MRS759142 F
362 REX640
Technical Manual