EasyManua.ls Logo

ABB RELION REX640 - 5.15.7.2 DNZSRDIR Output signals; 5.15.8 DNZSRDIR Settings

ABB RELION REX640
1960 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Name Type Default Description
BLOCK BOOLEAN 0=False Block signal for acti-
vating the blocking
mode
RCA_CTL BOOLEAN 0=False Relay characteristic
angle control
5.15.7.2 DNZSRDIR Output signals
Table 1224: DNZSRDIR Output signals
Name Type Description
RELEASE BOOLEAN Release signal if direction cri-
teria is satisified
DIRECTION Enum Direction information
5.15.8 DNZSRDIR Settings
Table 1225: DNZSRDIR Group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Release delay time 0...1000 ms 10 10 Release delay time
Directional mode
1=Non-directional
2=Forward
3=Reverse
2=Forward Directional mode
Characteristic an-
gle
-179...180 deg 1 60 Characteristic an-
gle
Max forward angle 0...180 deg 1 88 Maximum phase
angle in forward di-
rection
Min forward angle 0...180 deg 1 88 Minimum phase an-
gle in forward di-
rection
Max reverse angle 0...180 deg 1 88 Maximum phase
angle in reverse di-
rection
Min reverse angle 0...180 deg 1 88 Minimum phase an-
gle in reverse direc-
tion
Table 1226: DNZSRDIR Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Pol quantity
3=Zero seq. volt.
4=Neg. seq. volt.
3=Zero seq. volt. Reference quantity
used to determine
fault direction
1MRS759142 F Protection related functions