EasyManua.ls Logo

ABB RELION REX640 - 9.8.3 Functionality

ABB RELION REX640
1960 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9.8.2 Function block
Figure 882: Function block
9.8.3 Functionality
The autosynchronizer co-ordinator function ASCGAPC can be used as a coordinator
for the synchronization of any bus coupler or grid transformer incomer breakers
in the power network. ASCGAPC must be present on the relay configuration
together with the bus coupler or grid transformer autosynchronization functions
(ASNSCSYN) as well as in generator autosynchronization functions (ASGCSYN).
ASCGAPC performs the network topology determination to identify the
subnetworks within the whole network. It routes the voltage and frequency
difference values from the synchronizing CB to all the generator sources. It also
identifies the sources which are eligible to participate in matching the voltage and
Control functions
1MRS759142 F
1608 REX640
Technical Manual

Table of Contents

Other manuals for ABB RELION REX640

Related product manuals