Name Type Description
Q3 BOOLEAN Output 3
Q4 BOOLEAN Output 4
Q5 BOOLEAN Output 5
Q6 BOOLEAN Output 6
Q7 BOOLEAN Output 7
Q8 BOOLEAN Output 8
3.20.6.5 Settings
Table 227: TONGAPC Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
On delay time 1 0...3600000 ms 1 0 On delay time
On delay time 2 0...3600000 ms 1 0 On delay time
On delay time 3 0...3600000 ms 1 0 On delay time
On delay time 4 0...3600000 ms 1 0 On delay time
On delay time 5 0...3600000 ms 1 0 On delay time
On delay time 6 0...3600000 ms 1 0 On delay time
On delay time 7 0...3600000 ms 1 0 On delay time
On delay time 8 0...3600000 ms 1 0 On delay time
3.20.6.6 Monitored data
Table 228: TONGAPC Monitored data
Name Type Values (Range) Unit Description
T_LEFT1 FLOAT32 0...3600 s Time left 1
T_LEFT2 FLOAT32 0...3600 s Time left 2
T_LEFT3 FLOAT32 0...3600 s Time left 3
T_LEFT4 FLOAT32 0...3600 s Time left 4
T_LEFT5 FLOAT32 0...3600 s Time left 5
T_LEFT6 FLOAT32 0...3600 s Time left 6
T_LEFT7 FLOAT32 0...3600 s Time left 7
T_LEFT8 FLOAT32 0...3600 s Time left 8
3.20.6.7 Technical data
Table 229: TONGAPC Technical data
Characteristic Value
Operate time accuracy ±1.0% of the set value or ±20 ms
Basic functions 1MRS759142 F
248 REX640
Technical Manual