ABB RELION REX640 - 4.3.6.8 Signals; HIAPDIF Input signals; HIBPDIF Input signals

ABB RELION REX640
1960 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
P
V
W
( )436
5900
32
2
(Equation 196)
Based on
Equation 197
and
Equation 198
, the need for voltage-dependent resistor is
checked.
U
A
kV
max
= + +
25000
2000
5900 15 75 1 00 74 0( . . ) .
(Equation 197)
˘
( ) .u V V V kV= 2 2 436 74000 436 16 0
(Equation 198)
The voltage-dependent resistor (one for each phase) is needed in this case as the
voltage during the fault is higher than 2 kV.
The leakage current through the VDR at the stabilizing voltage can be available from
the VDR manual, assuming that to be approximately 2 mA at stabilizing voltage
Iu A 0 002.
(Equation 199)
The sensitivity of the protection can be recalculated taking into account the leakage
current through the VDR as per
Equation 200
.
I A A A A
prim
= + + 2000 0 035 10 0 0034 0 002 142( . . . )
(Equation 200)
4.3.6.8 Signals
HIAPDIF Input signals
Table 697: HIAPDIF Input signals
Name Type Default Description
I3P SIGNAL - Three-phase currents
BLOCK BOOLEAN 0=False Block signal for acti-
vating the blocking
mode
1MRS759142 F Protection functions
REX640
Technical Manual
783