Table 1418: CSMSQI Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Ps Seq A on delay
time
0...1800000 ms 100 0 Delay the activa-
tion of the alarm
and warning out-
puts for positive
sequence current
Ps Seq A off delay
time
0...1800000 ms 100 0 Delay the deactiva-
tion of the alarm
and warning out-
puts for positive
sequence current
Ng Seq A on delay
time
0...1800000 ms 100 0 Delay the activa-
tion of the alarm
and warning out-
puts for negative
sequence current
Ng Seq A off delay
time
0...1800000 ms 100 0 Delay the deactiva-
tion of the alarm
and warning out-
puts for negative
sequence current
Zro A on delay time 0...1800000 ms 100 0 Delay the activation
of the alarm and
warning outputs
for zero sequence
current
Zro A off delay time 0...1800000 ms 100 0 Delay the deactiva-
tion of the alarm
and warning out-
puts for zero se-
quence current
8.1.11.7 CSMSQI Monitored data
Table 1419: CSMSQI Monitored data
Name Type Values (Range) Unit Description
NgSeq-A:1 FLOAT32 0.00...40.00 xIn Measured negative se-
quence current
PsSeq-A:1 FLOAT32 0.00...40.00 xIn Measured positive se-
quence current
ZrSeq-A:1 FLOAT32 0.00...40.00 xIn Measured zero se-
quence current
I2_HIGH_AL BOOLEAN
0=False
1=True
Negative sequence high
alarm
I2_HIGH_WARN BOOLEAN
0=False
1=True
Negative sequence high
warning
I1_HIGH_AL BOOLEAN
0=False
1=True
Positive sequence high
alarm
I1_HIGH_WARN BOOLEAN
0=False
1=True
Positive sequence high
warning
I1_LOW_WARN BOOLEAN
0=False
1=True
Positive sequence low
warning
I1_LOW_AL BOOLEAN
0=False
1=True
Positive sequence low
alarm
I0_HIGH_AL BOOLEAN
0=False
1=True
Zero sequence high
alarm
Table continues on the next page
Measurement functions 1MRS759142 F
1474 REX640