Parameter Values (Range) Unit Step Default Description
6=MONTH
7=YEAR
7.3.9 HSARSPTR Monitored data
Table 1330: HSARSPTR Monitored data
Name Type Values (Range) Unit Description
HS_TOIL_GRA FLOAT32 0...1000 Rated hot spot to top
oil temperature gradi-
ent
LD_RSV_WRN_PCT FLOAT32 0.0...1000.0 % Percentage load reserve
for reaching warning
condition
LD_RSV_ALM_PCT FLOAT32 0.0...1000.0 % Percentage load reserve
for reaching alarm con-
dition
AGEING_RATE FLOAT32 0.00...50.00 Momentary relative
ageing rate
LOSS_OF_LIFE FLOAT32 0...100 Loss of life in years
AVG_AGE_RATE FLOAT32 0...100 Average ageing rate
over set time period
HSARSPTR Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
7.3.10 Technical data
Table 1331: HSARSPTR technical data
Characteristic Value
Warning/alarm time accuracy ±1.0 % of the set value or ±0.50 s
1MRS759142 F Condition monitoring functions
REX640
Technical Manual