ABB RELION REX640 - 4.2.9.9 MFADPSDE Monitored data

ABB RELION REX640
1960 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Values (Range) Unit Step Default Description
3=Reverse
Voltage start value 0.01...1.00 xUn 0.01 0.10 Voltage start value
Operate delay time 60...1200000 ms 10 500 Operate delay time
Table 620: MFADPSDE Group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Operating quantity
1=Adaptive
2=Amplitude
3=Resistive
1=Adaptive Operating quantity
selection
Min operate current 0.005...5.000 xIn 0.001 0.010 Minimum operate
current
Tilt angle 2.0...20.0 deg 0.1 5.0 Characteristic tilt
angle
Table 621: MFADPSDE Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Operation mode
1=Intermittent EF
2=Transient EF
3=General EF
4=Alarming EF
3=General EF Operation criteria
Table 622: MFADPSDE Non group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Peak counter limit 2...20 1 2 Peak counter limit
for restriking EF
Start delay time 30...60000 ms 1 30 Start delay time
Reset delay time 0...60000 ms 1 500 Reset delay time
Pol reversal
0=False
1=True
0=False Rotate polarizing
quantity
4.2.9.9 MFADPSDE Monitored data
Table 623: MFADPSDE Monitored data
Name
Type Values (Range) Unit Description
START_DUR FLOAT32 0.00...100.00 % Ratio of start time / op-
erate time
ANGLE FLOAT32 -180.00...180.00 deg Angle between polar-
izing and operating
quantity
I_OPER FLOAT32 0.000...40.000 xIn Calculated operating
current
MFADPSDE Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
1MRS759142 F Protection functions
REX640
Technical Manual
581