Parameter Values (Range) Unit Step Default Description
3=Reverse
Voltage start value 0.01...1.00 xUn 0.01 0.10 Voltage start value
Operate delay time 60...1200000 ms 10 500 Operate delay time
Table 620: MFADPSDE Group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Operating quantity
1=Adaptive
2=Amplitude
3=Resistive
1=Adaptive Operating quantity
selection
Min operate current 0.005...5.000 xIn 0.001 0.010 Minimum operate
current
Tilt angle 2.0...20.0 deg 0.1 5.0 Characteristic tilt
angle
Table 621: MFADPSDE Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Operation mode
1=Intermittent EF
2=Transient EF
3=General EF
4=Alarming EF
3=General EF Operation criteria
Table 622: MFADPSDE Non group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Peak counter limit 2...20 1 2 Peak counter limit
for restriking EF
Start delay time 30...60000 ms 1 30 Start delay time
Reset delay time 0...60000 ms 1 500 Reset delay time
Pol reversal
0=False
1=True
0=False Rotate polarizing
quantity
4.2.9.9 MFADPSDE Monitored data
Table 623: MFADPSDE Monitored data
Name
Type Values (Range) Unit Description
START_DUR FLOAT32 0.00...100.00 % Ratio of start time / op-
erate time
ANGLE FLOAT32 -180.00...180.00 deg Angle between polar-
izing and operating
quantity
I_OPER FLOAT32 0.000...40.000 xIn Calculated operating
current
MFADPSDE Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
1MRS759142 F Protection functions
REX640
Technical Manual
581