It is essential to provide power frequency overvoltage protection, in the form of
time delayed element, either IDMT or DT to prevent equipment damage.
4.5.1.8 Signals
PHPTOV Input signals
Table 782: PHPTOV Input signals
Name Type Default Description
U3P SIGNAL - Three-phase voltages
BLOCK BOOLEAN 0=False Block signal for acti-
vating the blocking
mode
PHPTOV Output signals
Table 783: PHPTOV Output signals
Name Type Description
OPERATE BOOLEAN Operate
START BOOLEAN Start
4.5.1.9 PHPTOV Settings
Table 784: PHPTOV Group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Start value 0.05...1.60 xUn 0.01 1.10 Start value
Time multiplier 0.025...15.000 0.005 1.000 Time multiplier
in IEC/ANSI IDMT
curves
Operate delay time 40...300000 ms 10 40 Operate delay time
Operating curve
type
5=ANSI Def. Time
15=IEC Def. Time
17=Inv. Curve A
18=Inv. Curve B
19=Inv. Curve C
20=Programmable
15=IEC Def. Time Selection of time
delay curve type
Table 785: PHPTOV Group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Type of reset curve
1=Immediate
2=Def time reset
1=Immediate Selection of reset
curve type
Type of time reset
1=Freeze Op timer
2=Decrease Op tim-
er
1=Freeze Op timer Selection of time
reset
Protection functions 1MRS759142 F
856 REX640
Technical Manual