3.21.6.4 Settings
The function does not have any parameters available in LHMI or PCM600.
3.21.7 Switching device status decoder CLOSE position
T_POS_CL, OPEN position T_POS_OP and OK status
T_POS_OK
3.21.7.1 Function block
Figure 169: Function blocks
3.21.7.2 Functionality
The circuit breaker position information can be communicated with the IEC 61850
GOOSE messages. The position information is a double binary data type which is
fed to the POS input.
T_POS_CL and T_POS_OP are used for extracting the circuit breaker status
information. Respectively, T_POS_OK is used to validate the intermediate or faulty
breaker position.
Table 302: Cross reference between circuit breaker position and function block
output
Circuit breaker
position
Output of the function block
T_POS_CL T_POS_OP T_POS_OK
Intermediate '00' FALSE FALSE FALSE
Close '01' TRUE FALSE TRUE
Open '10' FALSE TRUE TRUE
Faulty '11' TRUE TRUE FALSE
3.21.7.3 Signals
Table 303: T_POS_CL Input signals
Name Type Default Description
POS Double binary 0 Input signal
Table 304: T_POS_OP Input signals
Name Type Default Description
POS Double binary 0 Input signal
Basic functions 1MRS759142 F
296 REX640
Technical Manual