If the numbers of channels connected to U3P1...U3P4 and URES1...URES4
does not match with the number of connected SWITCH_TOx inputs, the
configuration of the function fails.
Outputs ALARM and URES_ALARM indicate bad quality data of system measurements
for selected U3P and URES, respectively.
Outputs WARNING and URES_WARNING indicate questionable quality data of system
measurements for selected U3P and URES, respectively.
Depending on the connected U3P channels to the voltage switch,
the
Primary voltage
settings between the source U3P must match.
Respectively, depending on the connected URES channels, the
Primary
voltage
settings between the source URES must match. Setting validation
for the primary voltages fails unless they are all stored simultaneously to
the protection relay.
3.20.16.6 Signals
Table 262: VMSWI Input signals
Name Type Default Description
U3P1 SIGNAL - Three-phase voltages
1
U3P2 SIGNAL - Three-phase voltages
2
U3P3 SIGNAL - Three-phase voltages
3
U3P4 SIGNAL - Three-phase voltages
4
URES1 SIGNAL - Residual voltage 1
URES2 SIGNAL - Residual voltage 2
URES3 SIGNAL - Residual voltage 3
URES4 SIGNAL - Residual voltage 4
SWITCH_TO2 BOOLEAN 0=False Switch to source 2
SWITCH_TO3 BOOLEAN 0=False Switch to source 3
SWITCH_TO4 BOOLEAN 0=False Switch to source 4
Table 263: VMSWI Output signals
Name Type Description
SOURCE1 BOOLEAN Selected voltage source is source 1
SOURCE2 BOOLEAN Selected voltage source is source 2
SOURCE3 BOOLEAN Selected voltage source is source 3
SOURCE4 BOOLEAN Selected voltage source is source 4
U3P SIGNAL Three-phase voltages
URES SIGNAL Residual voltage
ALARM BOOLEAN Alarm
WARNING BOOLEAN Warning
1MRS759142 F Basic functions
REX640
Technical Manual
277