PHIPTOC Input signals
Table 369: PHIPTOC Input signals
Name Type Default Description
I3P SIGNAL - Three-phase currents
BLOCK BOOLEAN 0=False Block signal for acti-
vating the blocking
mode
ENA_MULT BOOLEAN 0=False Enable signal for cur-
rent multiplier
PHLPTOC Output signals
Table 370: PHLPTOC Output signals
Name Type Description
OPERATE BOOLEAN Operate
START BOOLEAN Start
PHHPTOC Output signals
Table 371: PHHPTOC Output signals
Name Type Description
OPERATE BOOLEAN Operate
START BOOLEAN Start
PHIPTOC Output signals
Table 372: PHIPTOC Output signals
Name Type Description
OPERATE BOOLEAN Operate
START BOOLEAN Start
4.1.1.10 Settings
PHLPTOC Settings
Table 373: PHLPTOC Group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Start value 0.05...10.00 xIn 0.01 0.05 Start value
Start value Mult 0.8...10.0 0.1 1.0 Multiplier for scal-
ing the start value
Table continues on the next page
1MRS759142 F Protection functions
REX640
Technical Manual
339