Parameter Values (Range) Unit Step Default Description
Time multiplier 0.025...15.000 0.005 1.000 Time multiplier
in IEC/ANSI IDMT
curves
Operate delay time 40...300000 ms 10 40 Operate delay time
Operating curve
type
1=ANSI Ext. inv.
2=ANSI Very inv.
3=ANSI Norm. inv.
4=ANSI Mod. inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv.
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
20=UK rectifier
15=IEC Def. Time Selection of time
delay curve type
Table 374: PHLPTOC Group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Type of reset curve
1=Immediate
2=Def time reset
3=Inverse reset
1=Immediate Selection of reset
curve type
Table 375: PHLPTOC Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Num of start pha-
ses
1=1 out of 3
2=2 out of 3
3=3 out of 3
1=1 out of 3 Number of phases
required for oper-
ate activation
Curve parameter A 0.0086...50000.000
0
0.0001 28.2000 Parameter A for
customer program-
mable curve
Curve parameter B 0.0000...0.7120 0.0001 0.1217 Parameter B for
customer program-
mable curve
Curve parameter C 0.02...6.00 0.01 2.00 Parameter C for
customer program-
mable curve
Curve parameter D 0.46...30.00 0.01 29.10 Parameter D for
customer program-
mable curve
Curve parameter E 0.0...1.0 0.1 1.0 Parameter E for
customer program-
mable curve
Protection functions 1MRS759142 F
340 REX640
Technical Manual