7.2 Motor controlled earthing switch and disconnector
supervision ESDCSSWI (ANSI 29CM)
7.2.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Motor controlled earthing switch
and disconnector supervision
ESDCSSWI ESDCCM 29CM
7.2.2 Function block
Figure 784: Function block
7.2.3 Functionality
The motor controlled earthing switch and disconnector supervision (ESDCSSWI)
is used for monitoring switch status, inactivity, contact travel time and operation
counter. Function can be used for condition monitoring and as indicator for
maintenance need.
7.2.4 Operation principle
The
Operation
setting is used to enable or disable the function. When selected "On"
the function is enabled and respectively "Off" means function is disabled.
The operation of ESDCSSWI is described by using a module diagram (see figure
below). All the modules in the diagram are explained in the next sections.
Condition monitoring functions
1MRS759142 F