Loading...
9.9.10 Technical data
Table 1568: DARREC Technical data
Characteristic Value
Operate time accuracy ±1.0 % of the set value or ±20 ms
9.10 Tap changer control with voltage regulator
OL5ATCC (ANSI 90V)
9.10.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Tap changer control with voltage
regulator
OL5ATCC COLTC 90V
9.10.2 Function block
Figure 914: Function block symbol
9.10.3 Functionality
The tap changer control with voltage regulator function OL5ATCC (on-load tap
changer controller) regulates the voltage of power transformers with on-load
tap changers in distribution substations. OL5ATCC provides manual or automatic
voltage control of the power transformer by using the raising or lowering signals to
the on-load tap changer.
The automatic voltage regulation can be used in single or parallel transformer
applications. The parallel operation can be based on the Master/Follower principle
(M/F), Negative Reactance Principle (NRP) or Minimizing Circulating Current (MCC).
1MRS759142 F
Control functions
REX640
Technical Manual
1695