ABB RELION REX640 - 9.11.9.2 PASANCR Output signals

ABB RELION REX640
1960 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Name Type Default Description
COIL_STS BOOLEAN 0=False Connection status of
the variable arc sup-
pression coil
FIXCOIL_STS BOOLEAN 0=False Connection status of
the fixed coil
RESISTOR_STS BOOLEAN 0=False Connection status of
the parallel current
raising resistor
HIGH_LIMIT BOOLEAN 0=False High end position
reached
LOW_LIMIT BOOLEAN 0=False Low end position
reached
ST_CALIB BOOLEAN 0=False Rising edge of this
signal triggers the
calibration procedure
of the coil
ST_TUNING BOOLEAN 0=False Rising edge of this
signal triggers the au-
tomatic tuning proce-
dure
ST_RESIS_SEQ BOOLEAN 0=False Rising edge of this
signal triggers the
resistor control se-
quence
RAISE_LOCAL BOOLEAN 0=False Increase arc suppres-
sion coil current
LOWER_LOCAL BOOLEAN 0=False Decrease arc sup-
pression coil current
PARALLEL BOOLEAN 0=False Parallel controller has
coil movement in pro-
gress
BLK_AUTO BOOLEAN 0=False Blocking the coil au-
tomatic tuning
BLK_MANUAL BOOLEAN 0=False Blocking the coil man-
ual operation
BLK_RESISTOR BOOLEAN 0=False Disconnect and block
switching on the par-
allel resistor
HIGH_LIMIT BOOLEAN 0=False High coil position
LOW_LIMIT BOOLEAN 0=False Low coil position
Control functions 1MRS759142 F
1748 REX640
Technical Manual