4.2.2.13 Monitored data
DEFLPDEF Monitored data
Table 551: DEFLPDEF Monitored data
Name Type Values (Range) Unit Description
START_DUR FLOAT32 0.00...100.00 % Ratio of start time / op-
erate time
ANGLE_RCA FLOAT32 -180.00...180.00 deg Angle between operat-
ing angle and charac-
teristic angle
ANGLE FLOAT32 -180.00...180.00 deg Angle between polar-
izing and operating
quantity
I_OPER FLOAT32 0.00...40.00 xIn Calculated operating
current
DEFLPDEF Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
DEFHPDEF Monitored data
Table 552: DEFHPDEF Monitored data
Name
Type Values (Range) Unit Description
START_DUR FLOAT32 0.00...100.00 % Ratio of start time / op-
erate time
ANGLE_RCA FLOAT32 -180.00...180.00 deg Angle between operat-
ing angle and charac-
teristic angle
ANGLE FLOAT32 -180.00...180.00 deg Angle between polar-
izing and operating
quantity
I_OPER FLOAT32 0.00...40.00 xIn Calculated operating
current
DEFHPDEF Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
4.2.2.14 Technical data
Table 553: DEFxPDEF Technical data
Characteristic Value
Operation accuracy Depending on the frequency of the measured
current: f
n
±2 Hz
DEFLPDEF Current:
±1.5% of the set value or ±0.002 × I
n
Table continues on the next page
Protection functions 1MRS759142 F
480 REX640
Technical Manual

Table of Contents