EasyManua.ls Logo

ABB RELION REX640 - 6.9.7 Signals; 6.9.7.1 CTSRCTF Input signals

ABB RELION REX640
1960 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
used for the unit protection of a two-winding or three-winding transformer.
However, the function has a limitation that it cannot detect failure in case
of equipment under protection in no-load condition or when two simultaneous
secondary CT failures occur.
The detection of a zero current in any one phase is a partial indication of failure in
the current transformer secondary. Furthermore, if this current zero is due to the
failure in the current transformer secondary, it results in a change in the magnitude
of the negative-sequence current in the group only where current zero has been
detected. However, changes in the negative-sequence current in other groups of
three-phase current transformers at the instance of zero-current detection is an
indication of a system problem. Also, it may happen that after the detection of a
failure in the current transformer secondary, a fault may occur in the system. During
such condition, functions are internally blocked.
Phase discontinuity
A zero current detected due to the phase discontinuity results in an asymmetry in all
the sets of the current transformer, which then results in a change in the negative-
sequence current (ΔI
2
) in the healthy set. This change in the negative-sequence
current on the healthy sides, that is, other than where a zero current has been
detected, blocks the function.
In case of a lightly loaded transformer (up to 30 %) the change in the negative-
sequence current may be very negligible. However, a phase discontinuity results in
a change in the phase angle difference between two healthy phases in the set of
CTs where a zero current has been detected as well as on the primary side of the
transformer. This change in the value of the angle blocks the function internally.
Overload / System short circuit condition
It is required that any overload or short circuit conditions after a CT failure
should block the function. During overload or short circuit condition, the phase
current increases beyond its rated value; if any phase current on any set of current
transformer exceeds the set limit, the function is blocked internally. Also in case
of an unsymmetrical fault, the negative-sequence current increases. If the negative-
sequence current increases beyond the set limit, the function is blocked internally.
The overcurrent and negative-sequence current setting both can be set equal to the
overcurrent and negative-sequence protection function start value.
The internal blocking is thus useful for avoiding false operation during a fault
situation.
6.9.7 Signals
Supervision functions
1MRS759142 F
1356 REX640
Technical Manual

Table of Contents

Other manuals for ABB RELION REX640

Related product manuals