EasyManua.ls Logo

ABB RELION REX640 - 5 Protection related functions; 5.1 Three-phase inrush detector INRPHAR (ANSI 68 HB); 5.1.1 Identification; 5.1.2 Function block

ABB RELION REX640
1960 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5 Protection related functions
5.1 Three-phase inrush detector INRPHAR (ANSI 68HB)
5.1.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Three-phase inrush detector INRPHAR 3I2f> 68HB
5.1.2 Function block
Figure 656: Function block
5.1.3 Functionality
The three-phase inrush detector function INRPHAR is used to detect transformer
inrush situations in distribution networks.
Transformer inrush detection is based on the following principle: the output signal
BLK2H is activated once the numerically derived ratio of second harmonic current
I_2H and the fundamental frequency current I_1H exceeds the set value.
The operate time characteristic for the function is of definite time (DT) type.
The function contains a blocking functionality. Blocking deactivates all outputs and
resets timers.
5.1.4 Analog channel configuration
INRPHAR has one analog group input which must be properly configured.
Table 1103: Analog signals
Input Description
I3P Three-phase currents
1MRS759142 F Protection related functions
REX640
Technical Manual
1157

Table of Contents

Other manuals for ABB RELION REX640

Related product manuals