DEFHPDEF Output signals
Table 542: DEFHPDEF Output signals
Name Type Description
OPERATE BOOLEAN Operate
START BOOLEAN Start
FAULT_DIR Enum Detected fault direction
DIRECTION Enum Direction information
4.2.2.12 Settings
DEFLPDEF Settings
Table 543: DEFLPDEF Group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Start value 0.010...10.000 xIn 0.005 0.010 Start value
Start value Mult 0.8...10.0 0.1 1.0 Multiplier for scal-
ing the start value
Directional mode
1=Non-directional
2=Forward
3=Reverse
2=Forward Directional mode
Time multiplier 0.025...15.000 0.005 1.000 Time multiplier
in IEC/ANSI IDMT
curves
Operating curve
type
1=ANSI Ext. inv.
2=ANSI Very inv.
3=ANSI Norm. inv.
4=ANSI Mod. inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv.
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
15=IEC Def. Time Selection of time
delay curve type
Operate delay time 50...300000 ms 10 50 Operate delay time
Characteristic an-
gle
-179...180 deg 1 -90 Characteristic an-
gle
Max forward angle 0...180 deg 1 80 Maximum phase
angle in forward di-
rection