ABB RELION REX640 - 4.1.2.11 Monitored data; DPHLPDOC Monitored data

ABB RELION REX640
1960 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Values (Range) Unit Step Default Description
3=3 out of 3
Table 409: DPHHPDOC Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 1 20 Reset delay time
Minimum operate
time
20...60000 ms 1 20 Minimum operate
time for IDMT
curves
Allow Non Dir
0=False
1=True
0=False Allows prot activa-
tion as non-dir
when dir info is in-
valid
Measurement
mode
1=RMS
2=DFT
3=Peak-to-Peak
2=DFT Selects used meas-
urement mode
Min operate current 0.01...1.00 xIn 0.01 0.01 Minimum operating
current
Min operate volt-
age
0.01...1.00 xUn 0.01 0.01 Minimum operating
voltage
4.1.2.11 Monitored data
DPHLPDOC Monitored data
Table 410: DPHLPDOC Monitored data
Name
Type Values (Range) Unit Description
START_DUR FLOAT32 0.00...100.00 % Ratio of start time / op-
erate time
DIR_A Enum
0=unknown
1=forward
2=backward
-1=both
Direction phase A
DIR_B Enum
0=unknown
1=forward
2=backward
-1=both
Direction phase B
DIR_C Enum
0=unknown
1=forward
2=backward
-1=both
Direction phase C
ANGLE_A FLOAT32 -180.00...180.00 deg Calculated angle differ-
ence, Phase A
ANGLE_B FLOAT32 -180.00...180.00 deg Calculated angle differ-
ence, Phase B
ANGLE_C FLOAT32 -180.00...180.00 deg Calculated angle differ-
ence, Phase C
VMEM_USED BOOLEAN
0=False
1=True
Voltage memory in use
status
DPHLPDOC Enum
1=on
2=blocked
3=test
Status
Protection functions 1MRS759142 F
366 REX640
Technical Manual

Table of Contents