Parameter Values (Range) Unit Step Default Description
3=3 out of 3
Table 409: DPHHPDOC Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 1 20 Reset delay time
Minimum operate
time
20...60000 ms 1 20 Minimum operate
time for IDMT
curves
Allow Non Dir
0=False
1=True
0=False Allows prot activa-
tion as non-dir
when dir info is in-
valid
Measurement
mode
1=RMS
2=DFT
3=Peak-to-Peak
2=DFT Selects used meas-
urement mode
Min operate current 0.01...1.00 xIn 0.01 0.01 Minimum operating
current
Min operate volt-
age
0.01...1.00 xUn 0.01 0.01 Minimum operating
voltage
4.1.2.11 Monitored data
DPHLPDOC Monitored data
Table 410: DPHLPDOC Monitored data
Name
Type Values (Range) Unit Description
START_DUR FLOAT32 0.00...100.00 % Ratio of start time / op-
erate time
DIR_A Enum
0=unknown
1=forward
2=backward
-1=both
Direction phase A
DIR_B Enum
0=unknown
1=forward
2=backward
-1=both
Direction phase B
DIR_C Enum
0=unknown
1=forward
2=backward
-1=both
Direction phase C
ANGLE_A FLOAT32 -180.00...180.00 deg Calculated angle differ-
ence, Phase A
ANGLE_B FLOAT32 -180.00...180.00 deg Calculated angle differ-
ence, Phase B
ANGLE_C FLOAT32 -180.00...180.00 deg Calculated angle differ-
ence, Phase C
VMEM_USED BOOLEAN
0=False
1=True
Voltage memory in use
status
DPHLPDOC Enum
1=on
2=blocked
3=test
Status
Protection functions 1MRS759142 F
366 REX640
Technical Manual