3.1.2 Binary input settings
Table 8: Binary input settings
Parameter Values (Range) Unit Step Default Description
Slot specific threshold 0=False
1=True
0=False Use slot specific binary input
voltage threshold
Slot specific hysteresis 0=False
1=True
0=False Use slot specific binary input
voltage hysteresis
Input threshold voltage 16...176 Vdc 2 16 Global binary input threshold
for all slots
Input threshold hysteresis 10...50 % 2 10 Global binary input hysteresis
for all slots
Input osc. level 2...50 events/s 1 30 Binary input oscillation sup-
pression threshold
Input osc. hyst 2...50 events/s 1 10 Binary input oscillation sup-
pression hysteresis
3.1.3 Network1 address settings
Table 9: Non group settings
Parameter Values (Range) Unit Step Default Description
IP address 192.168.2.10 IP address for Net-
work1
Subnet mask 255.255.255.0 Subnet mask for
Network1
Default gateway 192.168.2.1 Default gateway for
Network1
Mac address XX-XX-XX-XX-XX-XX Mac address for
Network1
3.1.4 Network2 address settings
Table 10: Non group settings
Parameter Values (Range) Unit Step Default Description
Enable
0=False
1=True
0=False Enable Network2 IP
address
IP address 192.168.3.10 IP address for Net-
work2
Subnet mask 255.255.255.0 Subnet mask for
Network2
Default gateway 0.0.0.0 Default gateway for
Network2 (only in-
use if NW1 GW =
0.0.0.0)
Mac address XX-XX-XX-XX-XX-XX Mac address for
Network2
3.1.5 HMI port address settings
Basic functions 1MRS759142 F
58 REX640
Technical Manual

Table of Contents