EasyManua.ls Logo

ABB RELION REX640 - Setting of thermal restart level; Setting of thermal alarm level; 4.1.11.7 Signals; RPTTR Input signals

ABB RELION REX640
1960 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
and long-time thermal history, allowing more critical situations like motor start-ups
to be taken into consideration more carefully.
Setting of thermal restart level
The
Restart thermal Val
can be calculated as follows:
= 100%
100% +
(
)
(Equation 55)
For instance, if the start-up time of the motor is 4 seconds, and the calculated
operate time of the thermal protection stage for cold motor is 6 seconds, one
motor start-up will use 4/6 = 66.6% of the thermal capacity of the motor. Therefore,
the
Restart thermal Val
must be set to below 100% - 66.6% = 33.3% say to 28.3%
(100% - (66.6% + margin), where margin is 5%).
Setting of thermal alarm level
Tripping due to high overload can be avoided by reducing the load of the motor
when the thermal level reaches a set alarm level.
The
Alarm thermal value
can be set to a level, which will allow the use of the motor’s
full thermal capacity without causing a trip due to long time overload. Generally, the
Alarm thermal value
is set to 80….90% of the trip level.
4.1.11.7 Signals
RPTTR Input signals
Table 488: RPTTR Input signals
Name Type Default Description
I3P SIGNAL - Three-phase currents
U3P SIGNAL - Three-phase voltages
BLOCK BOOLEAN 0=False Block signal for acti-
vating the blocking
mode
START_EMERG BOOLEAN 0=False Signal for indicating
the need for emer-
gency start
AMB_TEMP FLOAT32 0 The ambient temper-
ature used in the cal-
culation
Protection functions 1MRS759142 F
432 REX640
Technical Manual

Table of Contents

Other manuals for ABB RELION REX640

Related product manuals