ABB RELION REX640 - Parallel unit detection and the MCC mode

ABB RELION REX640
1960 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 x Ici
I
TR1
x sin(φ
1
)
I
TR2
x sin(φ
2
)
φ
1
φ
2
U_A
Ici = circulating current
I
TR1
I
TR2
Figure 919: The circulating current between two parallel transformers
In this case, the circulating current can be calculated with the equation
I
I I
ci
TR TR
=
(sin sin )
φ φ
1 1 2 2
2
(Equation 378)
I
TR1
Current magnitude of regulator 1
I
TR2
Current magnitude of regulator 2
φ
1
Phase angle between U_A and I_A in regulator 1
φ
2
Phase angle between U_A and I_A in regulator 2
The circulating current can be read from the monitored data I_CIR.
Using the circulating current, the compensation term U
ci
can be calculated with the
equation
U
I
I
U
ci
ci
CT n
n
=
_ 1
100
Stability factor
(Equation 379)
I
ci
Circulating current
I
CT_n1
Nominal primary current of the CT
Stability
factor
Stability setting (the recommended value depends on the loop impedance)
The value of U
ci
, which can be positive or negative, is added to the
Band center
voltage Us
(
Equation 373
). According to
Figure 919
and
Equation 378
, the phasor
information from the other protection relays is needed.
1MRS759142 F
Control functions
REX640
Technical Manual
1711