Table 1439: RDRE Non group general settings (basic)
Parameter Values (Range) Unit Step Default Description
Operation 1=on
5=off
1 1=on Disturbance re-
corder on/off
Record length 10...500 fundamental cycles 1 50 Size of the record-
ing in fundamental
cycles
Pre-trg length 0...100 % 1 50 Length of the re-
cording preceding
the triggering
Table 1440: RDRE Non group general settings (advanced)
Parameter Values (Range) Unit Step Default Description
Operation mode 1=Saturation
2=Overwrite
1 1 Operation mode of
the recorder
Exclusion time 0...1 000 000 ms 1 0 The time during
which triggerings
of same type are
ignored
Storage rate 32, 16, 8 samples per funda-
mental cycle
32 Storage rate of
the waveform re-
cording
Periodic trig time 0...604 800 s 10 0 Time between peri-
odic triggerings
Stor. mode periodic 0=Waveform
1=Trend / cycle
1 0 Storage mode for
periodic triggering
Stor. mode manual 0=Waveform
1=Trend / cycle
1 0 Storage mode for
manual triggering
Table 1441: RDRE Control data (basic)
Parameter Values (Range) Unit Step Default Description
Trig recording
0=Cancel
1=Trig
0=Cancel
Trigger the disturb-
ance recording
Clear recordings
0=Cancel
1=Trig
0=Cancel
Clear all recordings
currently in memo-
ry
8.2.8 Monitored data
Table 1442: RDRE Monitored data
Parameter Values
(Range)
Unit Step Default Description
Number of re-
cordings
0...100 Number of re-
cordings cur-
rently in
memory
Rem. amount
of rec.
0...100 Remaining
amount of re-
cordings that
Table continues on the next page
Measurement functions 1MRS759142 F
1494 REX640
Technical Manual