EasyManua.ls Logo

ABB RELION REX640 - Fault current estimation and validity check

ABB RELION REX640
1960 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
where t
FLT
(1) equals the first time instant, when earth fault is detected by the GFC-
module. Pre-fault time moment is at least
Revert time
before earth fault occurrence
moment.
Revert time
setting should be set high enough (default value is 300 ms), because
during a high(er) ohmic fault the increase speed (gradient) of the magnitude of
U
o
may be slow, refer to example in
Figure 337
, where earth-fault occurs at time 0
ms. Earth fault is detected by GFC module slightly after that, at time instant t
FLT
(1)
marked with red dot, when magnitude of U
o
exceeds setting
Voltage start value
. As
an indication of detected earth-fault output EF_IND is activated.
Figure 337: Illustration of operation of General Fault Criterion (GFC) module and the meaning of
setting Revert time
In case of secondary testing of IFPTOC function, the pre-fault time in the
test file must be longer than
2xRevert time
. For example, if
Revert time
=
300 ms, then pre-fault time in the test file must be longer than 600 ms.
Indication of detected earth fault is available in Recorded data:
EF
indication
.
Fault current estimation and validity check
Operation of IFPTOC is based on estimating the magnitude of earth-fault current
flowing in the fault spot, or on touch voltage magnitude derived from the earth-
fault current estimate.
In compensated network, the magnitude of fundamental frequency earth-fault
current depends on the network damping (
I
d
), detuning (
I
v
), voltage (
U
PE
) and fault
resistance (
R
F
) and can be written as:
Protection functions
1MRS759142 F
588 REX640
Technical Manual

Table of Contents

Other manuals for ABB RELION REX640

Related product manuals