EasyManua.ls Logo

ABB RELION REX640 - 3.1.13 IEC 101-104 Secure statistics thresholds settings

ABB RELION REX640
1960 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 18: Non group settings
Parameter Values (Range) Unit Step Default Description
Protocol Security
Mode
1=App. authentica-
tion
2=TLS and appl.
auth.
0=Off
0=Off Protocol Security
Mode - 0: Off; 1:
Aplication authenti-
cation; 2: TLS and
Aplication authenti-
cation
Reply timeout 100...120000 ms 1 2000 Reply timeout
Exp Sesn key Chg
Intv
0...14400 s 1 1800 Expected Session
key change interval
- Value zero will in-
dicate that interval
is not used
Exp Sesn key Chg
Cnt
2...10000000 1 4000 Expected session
key change count
Max Sesn key Stat
Cnt
1...255 1 5 Maximum session
key status count
Sec Stat Cnt Grp
1=Group 1
2=Group 2
3=Group 3
4=Group 4
4=Group 4 Secure statistics
counter group
Sec Stat Cnt IOA 1...65535 1 61000 Information object
address for secure
statistics counters
3.1.13 IEC 101-104 Secure statistics thresholds settings
Table 19: Non group settings
Parameter Values (Range) Unit Step Default Description
Unexpected Msgs 1...65535 1 3 Security statistics
threshold for unex-
pected messages
Auth failures 1...65535 1 5 Security statistics
threshold for au-
thorization failures
Authn failures 1...65535 1 5 Security statistics
threshold for au-
thentication fail-
ures
Reply timeouts 1...65535 1 3 Security statistics
threshold for reply
timeouts
Rekeys Authn fail-
ure
1...65535 1 3 Security statistics
threshold for re-
keys due to authen-
tication failure
Total Msgs Tx 1...65535 1 100 Security statistics
threshold for total
messages sent
Total Msgs Rx 1...65535 1 100 Security statistics
threshold for total
messages received
Total Crit Msgs Rx 1...65535 1 100 Security statistics
threshold for total
critical messages
received
Discarded Msgs 1...65535 1 10 Security statistics
threshold discar-
ded messages
Table continues on the next page
1MRS759142 F Basic functions
REX640
Technical Manual
65

Table of Contents

Other manuals for ABB RELION REX640