9.1.6.3 ESXSWI Input signals
Table 1458: ESXSWI Input signals
Name Type Default Description
POSOPEN BOOLEAN 0=False Signal for open po-
sition of apparatus
from I/O
POSCLOSE BOOLEAN 0=False Signal for close po-
sition of apparatus
from I/O
ENA_OPEN BOOLEAN 1=True Enables opening
ENA_CLOSE BOOLEAN 1=True Enables closing
BLK_OPEN BOOLEAN 0=False Blocks opening
BLK_CLOSE BOOLEAN 0=False Blocks closing
AU_OPEN BOOLEAN 0=False Auxiliary open
AU_CLOSE BOOLEAN 0=False Auxiliary close
ITL_BYPASS BOOLEAN 0=False Discards ENA_OPEN
and ENA_CLOSE in-
terlocking when TRUE
9.1.6.4 CBXCBR Output signals
Table 1459: CBXCBR Output signals
Name Type Description
SELECTED BOOLEAN Object selected
EXE_OP BOOLEAN Executes the command for
open direction
EXE_CL BOOLEAN Executes the command for
close direction
OP_REQ BOOLEAN Open request
CL_REQ BOOLEAN Close request
OPENPOS BOOLEAN Apparatus open position
CLOSEPOS BOOLEAN Apparatus closed position
OKPOS BOOLEAN Apparatus position is ok
OPEN_ENAD BOOLEAN Opening is enabled based on
the input status
CLOSE_ENAD BOOLEAN Closing is enabled based on
the input status
CTL_ITL_BLKD BOOLEAN Control is blocked due to in-
terlocking
Control functions 1MRS759142 F