5.8.7.1 CVPSOF Input signals
Table 1169: CVPSOF Input signals
Name Type Default Description
I3P SIGNAL - Three-phase currents
U3P SIGNAL - Three-phase voltages
BLOCK BOOLEAN 0=False Block signal for acti-
vating the blocking
mode
CB_CL_CMD BOOLEAN 0=False External enabling of
SOTF by CB close
command
START BOOLEAN 0=False Start from function
to be accelerated by
SOTF
START_DLYD BOOLEAN 0=False Start from function
to be accelerated
with delay by SOTF
5.8.7.2 CVPSOF Output signals
Table 1170: CVPSOF Output signals
Name Type Description
OPERATE BOOLEAN Operate
5.8.8 CVPSOF Settings
Table 1171: CVPSOF Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Table 1172: CVPSOF Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Operation mode
1=Start
2=Current&voltage
3=Both
3=Both Mode of operation
of SOTF Function
SOTF initialization
1=SwitchCommand
-2=Voltage or
SwitchCmd
-3=Current or
SwitchCmd
-4=Cur&Vol or
SwitchCmd
-2=Voltage or
SwitchCmd
Switch onto fault
initialization
Table continues on the next page
Protection related functions 1MRS759142 F
1228 REX640
Technical Manual

Table of Contents