EasyManua.ls Logo

ABB RELION REX640 - 9.3.6.2 P3 SSXSWI Output signals; 9.3.7 P3 SSXSWI Settings

ABB RELION REX640
1960 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9.3.6.1 P3SSXSWI Input signals
Table 1486: P3SSXSWI Input signals
Name Type Default Description
DCPOSOPEN BOOLEAN 0=False Signal for open posi-
tion of disconnector
DCPOSCLOSE BOOLEAN 0=False Signal for close posi-
tion of disconnector
ESPOSOPEN BOOLEAN 0=False Signal for open po-
sition of earthing
switch
ESPOSCLOSE BOOLEAN 0=False Signal for close po-
sition of earthing
switch
REED BOOLEAN 0=False Signal for close posi-
tion of reed contact
9.3.6.2 P3SSXSWI Output signals
Table 1487: P3SSXSWI Output signals
Name Type Description
DCOPEN_POS BOOLEAN Disconnector in open posi-
tion
DCCLOSE_POS BOOLEAN Disconnector in closed posi-
tion
ESOPEN_POS BOOLEAN Earthing switch in open posi-
tion
ESCLOSE_POS BOOLEAN Earthing switch in closed po-
sition
OKPOS BOOLEAN Apparatus position is ok
9.3.7 P3SSXSWI Settings
Table 1488: P3SSXSWI Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Reed contact
0=Not available
1=Available
0=Not available Availability of reed
contact
Identification P3SSXSWI1 switch
position
Control object
identification
Control functions 1MRS759142 F
1538 REX640
Technical Manual

Table of Contents

Other manuals for ABB RELION REX640