Parameter Values (Range) Unit Step Default Description
Serial number 0 External equipment
serial number
Model 0 External equipment
model
9.2.8 P3SXSWI Monitored data
Table 1483: P3SXSWI Monitored data
Name Type Values (Range) Unit Description
POSITION Enum
0=earthing switch
closed
1=earthing switch inter-
mediate
2=both open
3=disconnector inter-
mediate
4=disconnector closed
5=faulty
3-position switch posi-
tion
POSITION_DC Dbpos
0=intermediate
1=open
2=closed
3=faulty
Disconnector position
POSITION_ES Dbpos
0=intermediate
1=open
2=closed
3=faulty
Earthing switch posi-
tion
SWTYPE Enum
1=3-position switch
2=Disconnector
3=Earthing switch
4=Unknown
Switch type
9.2.9 Technical revision history
Table 1484: P3SXSWI Technical revision history
Product
connectivi
ty level
Technical
revision
Change
PCL4 B
New output CTL_ITL_BLKD and pulse timer setting
Interlocking
Pls Len
added.
1MRS759142 F Control functions