4.5.2.8 Signals
PHPTUV Input signals
Table 794: PHPTUV Input signals
Name Type Default Description
U3P SIGNAL - Three-phase voltages
BLOCK BOOLEAN 0=False Block signal for acti-
vating the blocking
mode
PHPTUV Output signals
Table 795: PHPTUV Output signals
Name Type Description
OPERATE BOOLEAN Operate
START BOOLEAN Start
4.5.2.9 PHPTUV Settings
Table 796: PHPTUV Group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Start value 0.05...1.20 xUn 0.01 0.90 Start value
Time multiplier 0.025...15.000 0.005 1.000 Time multiplier
in IEC/ANSI IDMT
curves
Operate delay time 20...300000 ms 10 60 Operate delay time
Operating curve
type
5=ANSI Def. Time
15=IEC Def. Time
21=Inv. Curve A
22=Inv. Curve B
23=Programmable
15=IEC Def. Time Selection of time
delay curve type
Table 797: PHPTUV Group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Type of reset curve
1=Immediate
2=Def time reset
1=Immediate Selection of reset
curve type
Type of time reset
1=Freeze Op timer
2=Decrease Op tim-
er
1=Freeze Op timer Selection of time
reset
Table 798: PHPTUV Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation
1=on
1=on Operation Off / On
Table continues on the next page