ABB RELION REX640 - LNPLDF Output signals; 4.3.1.9 LNPLDF Settings

ABB RELION REX640
1960 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Name Type Default Description
BLOCK_LS BOOLEAN 0=False Signal for blocking
the stab. stage
ENA_MULT_HS BOOLEAN 0=False Enables the high
stage multiplier
LNPLDF Output signals
Table 648: LNPLDF Output signals
Name Type Description
OPERATE BOOLEAN Operate, local or remote,
stabilized or instantaneous
stage
START BOOLEAN Start, local or remote
STR_LS_LOC BOOLEAN Start stabilized stage local
STR_LS_REM BOOLEAN Start stabilized stage remote
OPR_LS_LOC BOOLEAN Operate stabilized stage local
OPR_LS_REM BOOLEAN Operate stabilized stage re-
mote
OPR_HS_LOC BOOLEAN Operate instantaneous stage
local
OPR_HS_REM BOOLEAN Operate instantaneous stage
remote
BLKD2H_LOC BOOLEAN Restraint due 2nd harmonics
detected local
BLKD2H_REM BOOLEAN Restraint due 2nd harmonics
detected remote
PRO_ACTIVE BOOLEAN Status of the protection, true
when function is operative
4.3.1.9 LNPLDF Settings
Table 649: LNPLDF Group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Low operate value 10...200 %Ir 1 10 Basic setting for
the stabilized stage
start
High operate value 200...4000 %Ir 1 2000 Instantaneous
stage operate value
Start value 2.H 10...50 % 1 20 The ratio of the
2. harmonic com-
ponent to funda-
mental component
required for block-
ing
High Op value Mult 0.5...1.0 0.1 1.0 Multiplier for scal-
ing the high stage
operate value
Table continues on the next page
Protection functions 1MRS759142 F
676 REX640
Technical Manual