- If the frequency difference reaches the target value "± Smax/2" with the
hysteresis band specified by the settings
Freq Diff Ov Synch
and
Freq Diff
sub Synch
, the raise and lower commands are reset.
During matching of network CB synchronization
- If any of the governor limit alarms GOV_ALM_HI or GOV_ALM_LO is TRUE, the
raise and lower commands are reset.
- When the generator is selected for fine tuning, if the frequency difference
reaches to target value "± Smax/2" with the hysteresis band specified by the
settings
Freq Diff Ov Synch
and
Freq Diff sub Synch
, the raise and lower
commands are reset.
- When the generator is selected for coarse tuning, if the frequency difference
reaches within the limits of
Coarse Freq Diff Ov
and
Coarse Freq Diff sub
, the
raise and lower commands are reset.
When the matching is done for its own CB synchronization, the output MATCH_OK
is activated if the measured voltage and frequency differences are within the set
synchro check limits. The MATCH_INPRO output is active while the matching is in
progress.
When the matching is done for network CB synchronization, the monitored data
NTWMATCH_OK is activated if the network breaker voltage and frequency differences
are within the set match limits. NTWMATCH_PRO is active while the matching is in
progress. NTWMATCH_OK and NTWMATCH_PRO are available in the Monitored data
view.
Frequency rate of change tuning
When the control command parameter
Tune V and F match
is set to "Freq match
rate", the function calculates the generator frequency matching rate (dF/dt). The
calculated frequency matching rate is stored to the nonvolatile memory output
FREQ_CHG_RTE and is available in the Monitored data view. Once stored, the value
from FREQ_CHG_RTE can be used to set the setting
Freq rate of change
.
This tune frequency matching rate proceeds as follows:
1. The slip is adjusted until this lies in the range of +1...+3 %, then the adjusting
pulse is discontinued.
2. Ten seconds after the first adjusting pulse, the slip s0 is measured, then a
frequency raise command RAISE_F lasting 3 s is given. Ten seconds after the
end of the pulse, the slip s is measured and df/dt is calculated according to the
formula
df
dt
s s
=
0
3
(Equation 365)
3. With this df/dt value, the slip is brought back to approximately +2 %.
Ten seconds later, the slip is brought to 0 % with the same df/dt value. After
ten seconds, df/dt is calculated again and shown as monitored data output
FREQ_CHG_RTE.
The binary input BLOCK can be used to block the function. The activation of the
BLOCK input deactivates all binary outputs, binary monitored data and resets the
internal timers.