Name Type Values (Range) Unit Description
BLOCK BOOLEAN
0=False
1=True
Block signal for all bina-
ry outputs
HIGH_ALARM BOOLEAN
0=False
1=True
High alarm
HIGH_WARN BOOLEAN
0=False
1=True
High warning
LOW_WARN BOOLEAN
0=False
1=True
Low warning
LOW_ALARM BOOLEAN
0=False
1=True
Low alarm
I_INST_A FLOAT32 0.00...40.00 xIn IL1 Amplitude, magni-
tude of instantaneous
value
I_ANGL_A FLOAT32 -180.00...180.00 deg IL1 current angle
I_DB_A FLOAT32 0.00...40.00 xIn IL1 Amplitude, magni-
tude of deadband value
I_DMD_A FLOAT32 0.00...40.00 xIn Demand value of IL1
current
I_RANGE_A Enum
0=normal
1=high
2=low
3=high-high
4=low-low
IL1 Amplitude range
I_INST_B FLOAT32 0.00...40.00 xIn IL2 Amplitude, magni-
tude of instantaneous
value
I_ANGL_B FLOAT32 -180.00...180.00 deg IL2 current angle
I_DB_B FLOAT32 0.00...40.00 xIn IL2 Amplitude, magni-
tude of deadband value
I_DMD_B FLOAT32 0.00...40.00 xIn Demand value of IL2
current
I_RANGE_B Enum
0=normal
1=high
2=low
3=high-high
4=low-low
IL2 Amplitude range
I_INST_C FLOAT32 0.00...40.00 xIn IL3 Amplitude, magni-
tude of instantaneous
value
I_ANGL_C FLOAT32 -180.00...180.00 deg IL3 current angle
I_DB_C FLOAT32 0.00...40.00 xIn IL3 Amplitude, magni-
tude of deadband value
I_DMD_C FLOAT32 0.00...40.00 xIn Demand value of IL3
current
I_RANGE_C Enum
0=normal
1=high
2=low
3=high-high
4=low-low
IL3 Amplitude range
Measurement functions 1MRS759142 F