Table 1462: CBXCBR Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation mode
on/off
Select timeout 10000...300000 ms 10000 30000 Select timeout in
ms
Pulse length 10...60000 ms 1 200 Open and close
pulse length
Control model
0=status-only
1=direct-with-nor-
mal-security
4=sbo-with-en-
hanced-security
4=sbo-with-en-
hanced-security
Select control mod-
el
Operation timeout 10...6000000 ms 1 500 Timeout for nega-
tive termination
Identification CBXCBR1 switch
position
Control Object
identification
Table 1463: CBXCBR Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Operation counter 0...99999 1 0 Nr of opening oper-
ations
Adaptive pulse
0=False
1=True
1=True Deactivate control
pulse when appa-
ratus has reached
correct position
Event delay 0...10000 ms 1 200 Event delay of the
intermediate and
faulty position
Interlocking Pls Len 1...10 s 1 2 Pulse length for in-
terlocking violation
signal
Vendor 0 External equipment
vendor
Serial number 0 External equipment
serial number
Model 0 External equipment
model
9.1.7.2 DCXSWI Settings
Table 1464: DCXSWI Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation mode
on/off
Select timeout 10000...300000 ms 10000 30000 Select timeout in
ms
Pulse length 10...60000 ms 1 100 Open and close
pulse length
Control model
0=status-only
1=direct-with-nor-
mal-security
4=sbo-with-en-
hanced-security
4=sbo-with-en-
hanced-security
Select control mod-
el
Table continues on the next page
Control functions 1MRS759142 F
1516 REX640
Technical Manual