6.1.7 TCSSCBR Settings
Table 1241: TCSSCBR Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Operate delay time 1000...300000 ms 1 3000 Operate delay time
Table 1242: TCSSCBR Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Reset delay time 20...60000 ms 1 1000 Reset delay time
6.1.8 TCSSCBR Monitored data
Table 1243: TCSSCBR Monitored data
Name Type Values (Range) Unit Description
TCSSCBR Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
6.2 Current circuit supervision CCSPVC (ANSI CCM)
6.2.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Current circuit supervision CCSPVC MCS 3I CCM
6.2.2 Function block
Figure 744: Function block
Supervision functions
1MRS759142 F
1310 REX640
Technical Manual