ABB RELION REX640 - 4.1.10.9 MPTTR Monitored data

ABB RELION REX640
1960 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Values (Range) Unit Step Default Description
Negative Seq factor 0.0...10.0 0.1 0.0 Heating effect fac-
tor for negative se-
quence current
Weighting factor p 20.0...100.0 % 0.1 50.0 Weighting factor
(p)
Time constant nor-
mal
80...4000 s 1 320 Motor time con-
stant during the
normal operation
of motor
Time constant start 80...4000 s 1 320 Motor time con-
stant during the
start of motor
Time constant stop 80...60000 s 1 500 Motor time con-
stant during the
standstill condition
of motor
Env temperature
mode
1=FLC Only
2=Use input
3=Set Amb Temp
1=FLC Only Mode of measur-
ing ambient tem-
perature
Env temperature
Set
-20.0...70.0 °C 0.1 40.0 Ambient tempera-
ture used when
no external temper-
ature measurement
available
Table 481: MPTTR Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Table 482: MPTTR Non group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Current reference 0.30...2.00 xIn 0.01 1.00 Rated current (FLC)
of the motor
Initial thermal Val 0.0...100.0 % 0.1 74.0 Initial thermal level
of the motor
4.1.10.9 MPTTR Monitored data
Table 483: MPTTR Monitored data
Name
Type Values (Range) Unit Description
TEMP_AMB FLOAT32 -99...999 °C The ambient tempera-
ture used in the calcula-
tion
THERMLEV_ST FLOAT32 0.00...9.99 Thermal level at begin-
ning of motor startup
THERMLEV_END FLOAT32 0.00...9.99 Thermal level at the end
of motor startup situa-
tion
T_ENARESTART INT32 0...99999 s Estimated time to reset
of block restart
MPTTR Enum
1=on
2=blocked
3=test
4=test/blocked
Status
Table continues on the next page
Protection functions 1MRS759142 F
422 REX640
Technical Manual

Table of Contents